Question
How do I configure my AS950 relay outputs?
Answer
The following instructions may assist with the development of a relay output for the AS950 sampler.
Relay Output Signals
Some customers require relay outputs to be sent to their PLC or SCADA. On legacy model samplers (SD900 etc), pin F on the AUX port would send a 12 VDC signal to indicate 'Program Complete'. This feature was not incorporaterd into the AS950 sampler.
To initiate a relay output, the below instructions must be followed AND an IO module (IO9001 or IO9004) must be purchased.
IO9001 (Product # 9494500)
Includes:
IO9004 (Product # 9494600)
Includes:
** Note: on IO9001 & IO9004, if relay output and flow input will be used at the same time, the flow signal must be analogue.
Relay Output Programming Instructions
Enter the below on your AS950 unit:
Step 1: Configure the Sampler
STEP 2: Configure the Relay
Enter the below on your AS950 unit:
Relay output will now be set for chosen Relay (ie Relay 1, 2, 3 or 4).
Note: Number of relays will be limited to the IO900X module (shown above).
Wiring must be completed as per the wiring diagram. Additional wiring information provided in the IO900X user manual.

Relay Output Signals
Some customers require relay outputs to be sent to their PLC or SCADA. On legacy model samplers (SD900 etc), pin F on the AUX port would send a 12 VDC signal to indicate 'Program Complete'. This feature was not incorporaterd into the AS950 sampler.
To initiate a relay output, the below instructions must be followed AND an IO module (IO9001 or IO9004) must be purchased.
IO9001 (Product # 9494500)
Includes:
- Relay output x 1
- No analogue inputs or outputs.
- No digital inputs or outputs.
IO9004 (Product # 9494600)
Includes:
- Relay outputs x 4
- Analogue outputs x 3
- Analogue inputs x 3
- Digitial outputs x 0
- Digitial inputs x 0
** Note: on IO9001 & IO9004, if relay output and flow input will be used at the same time, the flow signal must be analogue.
Relay Output Programming Instructions
Enter the below on your AS950 unit:
Step 1: Configure the Sampler
- Select MENU
- Select HARDWARE SETUP
- Select AUX and I/O PORT
- Use UP ARROW to select TYPE
- Select IO900X
- Select AC RELAYS
- Select the required relays:
- AC Relay 1
- AC Relay 2
- AC Relay 3
- AC Relay 4
- Select SAVE
STEP 2: Configure the Relay
Enter the below on your AS950 unit:
- Select MENU
- Select PROGRAMMING
- Select ALARM PROGRAMMING
- Select SYSTEM ALARMS
- Select ADD NEW ALARM
- Select Alarm Type
- Program Start
- Program End
- Bottle Change
- Pump Forward
- Pump Reverse
- Sample Complete
- Entire Sample
- Missed Sample
- Purge Error
- Distributor Error
- Pump Fault
- Full Bottle
- Select Action Type
- Set Relay 1
- Set Relay 2
- Set Relay 3
- Set Relay 4
Relay output will now be set for chosen Relay (ie Relay 1, 2, 3 or 4).
Note: Number of relays will be limited to the IO900X module (shown above).
Wiring must be completed as per the wiring diagram. Additional wiring information provided in the IO900X user manual.
